3 Phase Motor Amperage Calculator

3 Phase Motor Amperage Formula:

\[ I = \frac{HP \times 746}{V \times \sqrt{3} \times PF \times Eff} \]

HP
V
(dimensionless)
(dimensionless)

Unit Converter ▲

Unit Converter ▼

From: To:

1. What is the 3 Phase Motor Amperage Formula?

The 3 Phase Motor Amperage Formula calculates the current (amperage) required by a three-phase motor based on its horsepower rating, operating voltage, power factor, and efficiency. This calculation is essential for proper electrical system design and motor protection.

2. How Does the Calculator Work?

The calculator uses the formula:

\[ I = \frac{HP \times 746}{V \times \sqrt{3} \times PF \times Eff} \]

Where:

Explanation: The formula converts mechanical power (HP) to electrical power requirements, accounting for three-phase power characteristics and motor performance factors.

3. Importance of Amperage Calculation

Details: Accurate amperage calculation is crucial for proper wire sizing, circuit breaker selection, motor protection device setting, and overall electrical system safety and efficiency.

4. Using the Calculator

Tips: Enter horsepower rating, operating voltage, power factor (typically 0.8-0.95), and motor efficiency (typically 0.8-0.95). All values must be positive numbers with power factor and efficiency between 0 and 1.

5. Frequently Asked Questions (FAQ)

Q1: Why is the power factor important in this calculation?
A: Power factor represents the phase difference between voltage and current. A lower power factor means the motor draws more current for the same power output, affecting electrical system design.

Q2: What are typical power factor values for motors?
A: Power factor typically ranges from 0.8 to 0.95 for three-phase induction motors, with higher values for larger and more efficient motors.

Q3: How does motor efficiency affect amperage?
A: Lower efficiency means more electrical power is required to produce the same mechanical output, resulting in higher current draw.

Q4: When should this calculation be used?
A: This calculation is essential during electrical system design, motor selection, circuit protection sizing, and troubleshooting motor performance issues.

Q5: Are there limitations to this formula?
A: This formula provides full-load current. Starting current (inrush current) can be 5-8 times higher and should be considered for circuit protection design.