Motor Horsepower To Amps Calculator

Three Phase Motor Current Formula:

\[ I = \frac{HP \times 746}{V \times \sqrt{3} \times PF \times Eff} \]

HP
volts
(dimensionless)
(dimensionless)

Unit Converter ▲

Unit Converter ▼

From: To:

1. What is the Three Phase Motor Current Formula?

The three phase motor current formula calculates the electrical current (amps) required by a three phase motor based on its horsepower rating, operating voltage, power factor, and efficiency. This calculation is essential for proper electrical system design and motor protection.

2. How Does the Calculator Work?

The calculator uses the three phase motor current formula:

\[ I = \frac{HP \times 746}{V \times \sqrt{3} \times PF \times Eff} \]

Where:

Explanation: The formula converts mechanical power (horsepower) to electrical power requirements, accounting for three phase power characteristics and motor efficiency losses.

3. Importance of Current Calculation

Details: Accurate current calculation is crucial for proper wire sizing, circuit breaker selection, motor protection device setting, and overall electrical system safety and efficiency.

4. Using the Calculator

Tips: Enter horsepower rating, operating voltage, power factor (typically 0.8-0.95), and motor efficiency (typically 0.8-0.95). All values must be positive numbers with power factor and efficiency between 0 and 1.

5. Frequently Asked Questions (FAQ)

Q1: Why is the conversion factor 746 used?
A: 746 watts equals 1 horsepower, so this factor converts mechanical power to electrical power requirements.

Q2: What is power factor and why is it important?
A: Power factor represents the ratio of real power to apparent power. Lower power factors require higher current for the same real power output.

Q3: How does motor efficiency affect current calculation?
A: Lower efficiency means more electrical input power is required to produce the same mechanical output, resulting in higher current draw.

Q4: When should this calculation be used?
A: This calculation is essential for electrical system design, motor starter selection, and ensuring proper protection for three phase AC motors.

Q5: Are there limitations to this formula?
A: This formula provides full-load current. Starting current (inrush current) is typically 5-7 times higher and should be considered for protection device selection.